How to pick the right replacement sensor — NPN vs PNP, NO vs NC, shielded vs unshielded — and swap it without guessing.
| Symptom | Likely cause | Action |
|---|---|---|
| Sensor never switches | Wiring type mismatch (NPN/PNP) or no supply | Verify output type against old sensor |
| Sensor always on | Sensing distance too short / target wrong | Check target material and gap |
| Intermittent switching | Loose M12 connector or cable break | Wiggle test, replace cable |
| False triggers from nearby metal | Unshielded sensor near metal mounting | Switch to shielded or flush type |
| LED flickers on power-up | Supply voltage drop or load short | Check 24V rail and load current |
We supply replacement sensors across proximity, photoelectric, pressure, temperature and encoder feedback types, in PNP/NPN and NO/NC variants. Send a photo of the old sensor's label and we match it exactly — including M12 cordsets and mounting brackets.
Yes, as long as the output type, mounting and response frequency match — a longer range only reduces sensitivity to target variation.
NPN switches the negative side (signal sinks to 0V); PNP switches the positive (source +24V). If unsure, send the old sensor photo and PLC input card model.
Yes — 3/4/5-pin cordsets in standard lengths, matched to the sensor's pinout.